首页产品高压电力电缆

40/69kV XLPE Insulated, PE Sheathed High Voltage Power Cables

Application

These single core cables are designed for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations. If the cable gets water inside due to the mechanical demages, swellable tapes prevent the movement of the water inside the cable.

Standard

IEC 60840

Construction

40/69kV XLPE Insulated, PE Sheathed High Voltage Power Cables
Conductor Aluminium wire, stranded to BS 6360 class 2.
Conductor Screen The conductor screen consists of an extruded layer of non metallic, semi-conducting compound applied on top of a semi-conducting tape. The conductor screen is applied under triple extrusion process over the conductor along with the insulation and the insulation screen. The extruded semi-conducting compound is firmly bonded to the insulation to exclude all air voids and can be easily hand stripped on site.
Insulation Extruded cross-linked polyethylene (XLPE-GP8) compound insulation.
Insulaton Screen The insulation screen consists of an extruded layer of non metallic, semi-conducting compound extruded over the insulation of each core. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating.
Semi-conductive Water Blocking Swellable Tape A semi-conducting tape shall be applied over the core assembly as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site. The screen may be covered by semi-conductive water blocking swellable tape to ensure longitudinal watertightness.
Metallic Layer The metallic layer may be applied over the core assembly collectively. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
Swellable Tape Swellable material
Separation Sheath Aluminum Tape sheath
Outer Sheath Thermoplastic HDPE-ST3 compound

Dimensional Data

Nom. Cross-Section Area Nom. Insulation Thickness Copper Wire Screen Area Approx. Overall Diameter Approx. Weight
CU AL
mm² mm mm² mm kg/m
240 13.0 25 56.9 4.7 2.9
300 13.0 25 59.9 5.4 3.3
400 13.0 35 61.5 6.4 4.0
500 13.0 35 65.0 8.4 4.9

Electrical Data

Nom. Cross-Section Area D C Resistance @20°C A C Resistance @90°C Capacitance per core Inductance Continuous Current Rating for Single Circuit (in air)
Cu conductor Al conductor
Cu Al Cu Al Trefoil Flat Trefoil Flat
mm² Ω/km Ω/km Ω/km Ω/km μF/km mH/km A A
240 0.0754 0.125 0.0973 0.161 0.174 0.414 576 715 449 557
300 0.0601 0.100 0.0781 0.129 0.189 0.397 658 820 515 642
400 0.0470 0.0778 0.0618 0.101 0.207 0.381 762 955 601 752
500 0.0366 0.0605 0.0492 0.0776 0.190 0.372 877 1108 753 838