NEK606 Offshore Marine Cable
P113 RFOU 18/30 (36)kV
Applications
These P113 RFOU 18/30 (36)kV NEK606 Offshore Marine cables are flame retardant, low smoke, halogen free and
mud resistant, used for fixed installation for medium voltage
power.
Standards
-
| IEC 60092-354 |
IEC 60092-360 |
| IEC 60332-1 |
IEC 60332-3-22 |
| IEC 60754-1,2 |
IEC 61034-1,2 |
| NEK 606:2016 |
|
Construction
- Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2 or class
5.
Conductor Screen: Semi conducting material.
Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
Insulation Screen: Semi conducting material and tinned copper wire braid.
Bedding: Halogen free compound.
Armour: Tinned copper wire braid in accordance with IEC 60092-350.
Outer Sheath: Halogen free thermosetting compound, SHF2 ,coloured red.
Electrical Characteristics
| Nominal Cross Section Area |
mm² |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
| Nominal Conductor Diameter |
mm |
5.1 |
6.5 |
7.4 |
8.7 |
10.3 |
12.2 |
13.8 |
15.1 |
17.0 |
19.6 |
21.9 |
| Maximum DC Resistant@20℃ |
Ω/km |
1.16 |
0.734 |
0.529 |
0.391 |
0.27 |
0.195 |
0.154 |
0.126 |
0.1 |
0.0762 |
0.0607 |
| Continuous Current Rating@45℃ 1 Core |
A |
96 |
127 |
157 |
196 |
242 |
293 |
339 |
389 |
444 |
522 |
601 |
| Continuous Current Rating@45℃ 3 Core |
A |
67 |
89 |
110 |
137 |
169 |
205 |
237 |
272 |
311 |
365 |
421 |
| Short Circuit Current 1s |
A |
2290 |
3580 |
5010 |
7150 |
10020 |
13590 |
17170 |
21460 |
26470 |
34340 |
42930 |
| Operating Voltage |
KV |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
18/30 |
Ambient Temperature Correction Factors
| Ambient Temperature Correction Factors |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
| Rating Factor |
1.1 |
1.05 |
1.0 |
0.94 |
0.88 |
0.82 |
0.74 |
0.67 |
0.58 |
0.47 |
Mechanical and Thermal Properties
Bending Radius: 15×OD (during installation); 9×OD (fixed installed)
Temperature Range: -20℃ ~ +90℃
Dimensions and Weight
| Construction No. of cores × Cross section |
Nominal Insulation Thickness |
Diameter under Armour |
Nominal Overall Diameter |
Nominal Weight |
| mm² |
mm |
mm |
mm |
kg/km |
| 1×50 |
8 |
33.8 |
41 |
2390 |
| 1×70 |
8 |
35.5 |
43 |
2700 |
| 1×95 |
8 |
37.3 |
45 |
3100 |
| 1×120 |
8 |
38.7 |
46 |
3430 |
| 1×150 |
8 |
40.1 |
48 |
3790 |
| 1×185 |
8 |
42 |
50 |
4310 |
| 1×240 |
8 |
45.5 |
53 |
5170 |
| 1×300 |
8 |
48.8 |
57 |
6020 |
| 3×50 |
8 |
70.6 |
81 |
7470 |
| 3×70 |
8 |
74.2 |
85 |
8530 |
| 3×95 |
8 |
78.1 |
89 |
9790 |
| 3×120 |
8 |
81.1 |
92 |
10760 |
| 3×150 |
8 |
84.2 |
95 |
11980 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing
process variations. For precise specifications or customized requirements, please contact us for further information.