Home ProuductsIndustrial Cables

TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded,
Armored 15KV, CSA HVTECK, 100% Ins. Level, 175 Mils,
Single Conductor

Application

These cables are used in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations, direct earth burial (with protection as required by inspection authority). They are exposed and concealed wiring in dry, damp or wet locations. Besides,the wires are in all hazardous locations when used with certified HL cable glands.

Standard:

CSA FT1 and FT4
IEEE 383 (70,000 BTU/hr)
UL 1581(70,000 BTU/hr)
IEEE 1202 (70,000 BTU/hr) CSA FT4
ICEA T-30-520 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
Hazardous location rating: HL
CSA Standard C68.3
CSA Standard C22.2 No. 174
CSA Approval (file) numbers: LR27161
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method

Cable Construction

Conductor: Bare copper Class B strand.
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor.
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE).
Insulation Shield: A semi-conducting thermosetting layer, applied in a triple extrusion process, plus a concentric serving of solid copper wires acting as both a drain wire shield and as a grounding (bonding) conductor—Black.
Ground (Bonding) Conductor: The conductor is a concentric serving of solid copper wires applied over the thermosetting insulation shield.
Inner Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Black.
Armor: Aluminum Interlocked Armor (AIA).
Overall Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option—Red.

5kv CSA HVTECK

Cable Parameter

NO.
of
CON.
CON.
Size
(AWG/
kcmil)
Ground
Wire Size
AWG
Nominal Diameter (over) Appr. Cable Weight
W/AL Armor
Ampacity
(40°C
Ambient)
Insulation Insulation
Shield
Inner
Jacket
Armor CABLE
Inches mm Inches mm Inches mm Inches mm Inches mm LBS/
1000
FT
kg/km In Air
1 2 6 0.66 16.7 0.73 18.6 0.99 25.3 1.24 31.5 1.33 33.8 950 1420 195
1 1 4 0.69 17.5 0.76 19.3 1.03 26.1 1.28 32.5 1.37 34.8 1080 1600 225
1 1/0 4 0.73 18.5 0.80 20.3 1.06 27.0 1.31 33.3 1.40 35.6 1170 1750 259
1 2/0 4 0.77 19.5 0.84 21.3 1.10 27.9 1.35 34.3 1.44 36.6 1290 1920 298
1 3/0 3 0.82 20.8 0.88 22.4 1.15 29.2 1.40 35.6 1.49 37.9 1470 2190 343
1 4/0 3 0.87 22.0 0.94 23.9 1.21 30.6 1.46 37.1 1.55 39.4 1640 2450 397
1 250 2 0.93 23.5 0.99 25.2 1.28 32.5 1.53 38.9 1.63 41.4 1900 2830 440
1 350 1 1.07 27.2 1.15 29.2 1.43 36.3 1.71 43.5 1.81 46.0 2370 3530 543
1 500 1/0 1.14 29.0 1.23 31.2 1.54 39.1 1.83 46.5 1.93 49.1 3080 4590 678
1 750 2/0 1.32 33.6 1.41 35.9 1.78 45.2 2.07 52.6 2.17 55.2 4240 6320 872
1 1000 2/0 1.48 37.6 1.57 39.9 1.93 49.0 2.22 56.4 2.32 59.0 5280 7860 1040