NEK606 Offshore Marine Cable
P124 RFOU/TFOU-FIRE RESISTANT 18/30 (36) kV

Applications

These P124 RFOU/TFOU-FIRE RESISTANT 18/30 (36) kV NEK606 Offshore Marine cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.

Standards

  • IEC 60092-354 IEC 60092-360
    IEC 60331-21 IEC 60332-1
    IEC 60332-3-22 IEC 60754-1,2
    IEC 61034-1,2 NEK 606:2016

  P124 RFOU/TFOU-FIRE RESISTANT 18/30 (36) kVNEK606 Marine Cable P124 RFOU/TFOU-FIRE RESISTANT 18/30 (36) kVNEK606 Marine Cable

Construction

  • Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2 or class 5.
    Conductor Screen : Semi conducting material.
    Insulation : Halogen-free EPR or XLPE.
    Insulation Screen : Semi conducting material and tinned copper wire braid.
    Bedding : Halogen free compound.
    Armour : Tinned copper wire braid.
    Outer Sheath : Halogen free thermosetting compound, SHF2, coloured red.
    Optional Fire protection : Extruded thermoplastic fire protection compound.
    Optional Taping : Lapped glass fibre tape.
    Optional Sheath : Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.

Electrical Characteristics

Nominal Cross Section Area mm² 70 95 120 150 185 240 300
Nominal Conductor Diameter mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9
Maximum DC Resistant@20℃ Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607
Continuous Current Rating@45℃ 1 Core A 242 293 339 389 444 522 601
Continuous Current Rating@45℃ 3 Core A 169 205 237 272 311 365 421
Short Circuit Current 1s A 10020 13590 17170 21460 26470 34340 42930
Operating Voltage KV 18/30 18/30 18/30 18/30 18/30 18/30 18/30

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties

Bending Radius : 20×OD (during installation); 12×OD (fixed installed)
Temperature Range : -20℃ ~ +90℃

Dimensions and Weight

Construction No. of cores × Cross section Nominal Insulation Thickness Nominal Diameter under armour Nominal Overall Diameter Nominal Weight
mm² mm mm mm kg/km
1×50 8.0 43 75.5 6210
1×70 8.0 45 77.5 6940
1×95 8.0 46 78.5 7390
1×120 8.0 48 80.5 7760
1×150 8.0 50 83 8405
1×185 8.0 53 86 9430
1×240 8.0 57 90 10540
1×300 8.0 81 114 13255
3×50 8.0 89 123 16520
3×95 8.0 95 129.5 19145
3×150 8.0 79.4 94 11090
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information.