HomeProuductsMining Cable

Mining Cable
Type G-GC Three-Conductor Portable Power Cable 2kV

Applications

These Type G-GC Three-Conductor Portable Mining Power cables are suitable for use with mobile mining equipment such as continuous miners, drills, cutters, loading machines, AC shuttle cars and pumps. Type G-GC is for applications where grounding conductors and a ground check conductor are required.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33
  • CAN/CSA-C22.2 No.96

Construction

Type G-GC mining Cable 2kV

  • Conductors: Stranded annealed tinned copper conductor.
  • Insulation:EPR.
  • Ground Check Conductor:Tinned copper conductor with a yellow polypropylene insulation.
  • Grounding Conductor:Tinned copper conductor.
  • Sheath: Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered as an option.

Options:
Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

  • Minimum Bending Radius: 6×OD
  • Maximum Operating Temperature: +90℃

Dimensions and Weight:

Construction No. of Strands Grounding Conductor Size Ground Check Conductor Size Nominal Insulation Thickness Nominal Overall Diameter Nominal Weight Ampacity
No. of cores×AWG/kcmil - AWG/kcmil AWG/kcmil inch mm inch mm lbs/kft kg/km A
3×8 133 10 10 0.06 1.5 0.97 24.6 600 893 59
3×6 133 10 10 0.06 1.5 1.05 26.7 735 1094 79
3×4 259 8 10 0.06 1.5 1.19 30.2 1065 1585 104
3×3 259 8 10 0.06 1.5 1.25 31.8 1245 1853 120
3×2 259 7 10 0.06 1.5 1.34 34.0 1480 2202 138
3×1 259 6 8 0.08 2.0 1.51 38.4 1885 2805 161
3×1/0 266 5 8 0.08 2.0 1.65 41.9 2290 3408 186
3×2/0 329 4 8 0.08 2.0 1.75 44.5 2710 4033 215
3×3/0 418 2 8 0.08 2.0 1.89 48.0 3270 4866 249
3×4/0 532 2 8 0.08 2.0 2.04 51.8 3975 5915 287
3×250 627 2 6 0.095 2.4 2.39 60.7 4950 7366 320
3×350 888 1/0 6 0.095 2.4 2.68 68.1 6625 9859 394
3×500 1221 2/0 6 0.095 2.4 3.03 77.0 8890 13230 487

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381